Technical Bulletin # C-05


Proof That Draining Down Condenser Water Piping
Will More Than Double Its Corrosion Rate



THE PROBLEM:

     It is a generally recognized fact that fully drained or partially drained piping systems are far more susceptible to corrosion than systems containing treated water, or even untreated water. Given a moist environment in combination with the presence of abundant air and oxygen, exposed piping has been documented to corrode at a rate two to ten times that of other water filled pipe of the same type, and located within the same circulating system. Condenser water systems suffer the greatest.

     In cases where condenser water piping is drained down within the interior of a building to protect it from freezing, it is common to measure significantly higher corrosion rates at the rooftop or outside level. In many cases, roof level piping may require replacement many decades before the remainder of the system. The buckets of scale typically removed from strainers and condenser heads every spring start-up are partially the result of such higher off-season corrosion activity.

     Ironically, corrosion coupon racks, often the only form of corrosion monitoring used, are rarely installed in outdoor or roof level locations. And if they are, the coupons are generally removed during the off-season. See Technical Bulletin # C-01 about the limitations of corrosion coupons.

     Of course, corrosion at the outer surface of the exposed rooftop pipe will also occur if not properly coated and protected - a maintenance problem often identified as a contributing factor to an overall higher measured corrosion rate. However, it is generally the piping interior which, having been totally or partially drained over many years, places the piping at greatest risk of advanced failure.

     The below comparison of wall thickness measurements and estimated corrosion rates from our ultrasonic pipe analysis of a New York City commercial property clearly illustrates the differences which, to some degree, always exists between drained and filled piping at the same exact condenser water system.

     In this example, the left side of the page represents test results taken from an ultrasonic evaluation of a section of 18 in. extra heavy condenser water pipe located in the sub-basement machine room area of a New York City office building, and never drained of treated water.

     The right side of the page represents the same exact pipe at the 30th floor shaftway, where it has been drained every single year during its five month winter season. The pipe is the same in all respects, has an initially specified wall thickness of 0.500 in., a history of excellent water treatment maintenance, and has been in service for over 45 years. Descriptions of the various charts and bar graphs precede each set of report data.


Comparison # 1 - Wall Thickness Measurements

     In a direct comparison of current wall thickness measurements, test results show significantly lower remaining pipe metal at the drained test site to the right. Also, the greater deviation between thickness measurements at the drained piping illustrates the much higher level of pitting activity at that location. Please note the differing scales for wall thickness at the left side of each graph.


Filled Pipe

Drained Pipe




Comparison # 2 - Average Corrosion Rates

     The below calculations are based upon the average of all recorded ultrasonic wall thickness measurements taken above. Differences in average measured pipe thickness, corrosion rate, and remaining pipe life life are dramatic. Annual draining of this system has actually increased the average corrosion rate of the roof level piping FOUR TIMES over that of the rest of the system. As a result, the lifetime of the piping has been reduced by nearly TEN FOLD!


Filled Pipe

Drained Pipe




Comparison # 3 - Maximum Corrosion Rates

     The below tables show the same basic set of calculations as in Comparison # 2, except that they are based upon the lowest measured wall thickness value of each set. Such data represents a weak link or worst case scenario, and offers an estimate of when the most aggressive corrosion will deteriorate the piping past its safe recommended limit.

     Shown here, differences in corrosion rate, retirement date, etc. are even more pronounced. In fact, the minimum wall thickness of the filled pipe significantly exceeds the standard specifications of any new pipe installed today, while the upper pipe exists at nearly HALF that value.


Filled Pipe

Drained Pipe




Comparison # 4 - Original vs. Remaining Values

     While the original pipe wall thickness and minimum allowable thickness values remain constant for both test locations, a major difference is obvious in the amount of pipe remaining. For the subject property, testing indicates that the minimum measured pipe wall thickness of the drained piping is nearing its minimum allowable safe operating limit.


Filled Pipe

Drained Pipe


THE SOLUTION:

     There are currently only three feasible ways to reduce the corrosion rate within a system which is partially or fully drained during part of the year. The easiest, though least effective, is to increase the level of the standard chemical inhibitor 2, 3 or more times just prior to draining. This leaves a heavier coating of standard inhibitor on the piping to provide partial protection against oxidation.

     A second method is to introduce a supplemental chemical inhibitor specifically formulated for the purpose of preventing corrosion during lay-up periods. Numerous formulations exist, including the newest development of powders called Vapor Corrosion Inhibitors (VCI). These place a protective and penetrating layer of inhibitor on the the surface of the metal to provide virtually complete corrosion control. See Technical Bulletin # P-05 for further information on VCI corrosion inhibitors.

     A third rarely used, but highly effective method, is to fill the empty system with a blanket of nitrogen gas, displacing the air and oxygen, and stopping the corrosion process almost entirely.

     An extremely critical step prior to any lay-up procedure is to chemically clean and sterilize the entire system. By removing unwanted rust, dirt, and biological matter, all of the above inhibitor methods will work much more effectively due to the increased amount of contact between inhibitor and base metal.



Request Further Information On A Specific
Application Or Operating Problem


Turn Back One Page




Main Page        Testing Services        Technical Bulletins        Case Histories
Business Opportunities        Specialty Products        Recommended Links
Request Information        Mailing List        About ECI        Contact Us

© Copyright 2000